Home Page Products Engineering/Tech Support Purchasing Site Map
Comfort Air And Refrigeration (HVACR) Fire Suppression Agents Oxygen Toxic Gases Product Index Brochures
SSG-MCD Predat-IR Built-In Options Accessories





The SSG-MCD Suppression System Guard replaces the
SSG Supression System Guard Monitors





SSG-MCD Models

SSG1: 1 Zone 3 Alarm levels
SSG4: 4 Zone 3 Alarm levels
SSG8: 8 Zone 3 Alarm levels
SSG16: 16 Zone 3 Alarm levels
SSG-MCD Custom Configuration

SSG Critical Environment
Monitoring Systems

Features
  • Factory Mutual (FM) Approval Pending
  • Detects Halon1301 and FM-200 Fire Suppression Agents
  • Detects all halogen based refrigerants
  • Compound type can be field changed without recalibration
  • Continuous digital display of system status
  • Analog output for remote monitoring
  • System malfunction detection and indication
  • Visual alarm indication
  • Sampling points can be located up to 250 feet (76 meters) from unit
  • Fresh air inlet for automatic rezeroing
  • Individually adjusted alarm points for each gas type being monitored
  • Multizone capability at a modest premium over single zone units

The SSG Monitors are advanced early warning loss detection and prevention monitoring systems designed specifically for fire suppression systems.

SenTech's SSG models are cost effective, self-contained monitors of halogenated gases that activate an alarm at a preset concentration that is programmed by the user. The Series includes single, four and eight zone models. SenTech's unique built in leak wait period minimizes nuisance false alarms.

SenTech SSG monitors provide 24/7 protection.

The SSG systems are based on an advanced infrared technology that can detect multiple gas types at concentration levels as low as one part per million (PPM).

The SSG Monitoring System reduces the risk of accidental suppression agent discharges by continuously sampling the air for halogenated compounds. In critical environments, Halon and FM-200 discharges occur more frequently by accident than by fire. The primary cause of agent discharges is refrigerant leaks from supporting air conditioning systems. By installing a SenTech SSG Monitoring System, this costly scenario can be avoided. One SSG Monitoring System can sample up to 16 zones and can be field programmed for various refrigerants and types of agents providing the earliest warning leak detection available today.

The SSG Monitoring System can interface with existing suppression system panels to automatically abort a Halon discharge due to a refrigerant leak, thus preventing the costly replacement of agents, and minimizing risks of downtime associated with a Halon system discharge.

SenTech's SSG Monitoring System is a cost effective solution for preventing critical downtime, avoiding business disruptions and suppressing system equipment failures.

Specifications

Sensitivity
As low as 1 PPM

Weight
32 lbs, (14.4 Kgs)

Power Requirements
120/240 Volt 50/60 Hz

Range
0 to 1000 PPM

Alarm Trip Points
Low Alarm 0 to 100% of Full Scale
Main Alarm 0 to 100% of Full Scale
High Alarm fixed at 100% of Full Scale

Operating Environmental Range
32o - 125o Fahrenheit
0o - 50o Celsius

Alarm Outputs
Indicator Light
3 Alarm Relays with 4 Form C contacts
(5 amps maximum each)

Options/Accessories
  • Remote transmitters: Oxygen & Toxic Gases
  • Remote PPM indicator w/ Audible silent switch
  • Strobe light, horn, strobe/horn combination
  • Zone pickup tubing

Home Page Products Engineering/Tech Support Purchasing Site Map